High-Rise Firefighting / Standpipe Operations: Engine Company Weapon Selection

There is a long list of strategic and tactical priorities for firefighting operations in high-rise buildings.  However, as with all fires, the need to get water on, and control the fire as quickly as possible, is by far the most critical component to a successful operation.  At high-rise fires, our fire attack almost always requires the use of a standpipe system.  There are several factors, many of which we have little or no control over, that can negatively affect our high-rise fire attack operation.  Ultimately, getting water on the fire quickly (at a high-rise) is often times much easier said than done.

My first piece of advice for firefighters, company officers, and chief officers who respond to and operate at high-rise and standpipe equipped buildings, is to be very skeptical of the buildings built-in fire protection systems, most specifically, the standpipe system.  Upon arrival at a high-rise fire, or any fire in a multi-story building that will require a standpipe system for fire attack, there should be a huge question mark at the forefront of our fireground size-up analysis.  That question is:  Will this standpipe system perform as required to aide and assist us with fire attack, or will there be system failures, which might lead to operational failure?  In many cases, part of the failure involves the size of hose that is brought into the building, on the false assumption that it will work in conjunction with the standpipe system.

Take just one moment to do a quantitative analysis of the potential problem.  Let me use my city as an example. In the City and County of Denver there are over four hundred high-rise buildings (75-foot or greater above lowest fire department access).  In addition, there are hundreds of other standpipe equipped, low-rise buildings.  All totaled, this represents a significant number of standpipe-equipped buildings, similar to what might be found in many large cities across the fire service.

Now, taking this a step further, within these hundreds of standpipe equipped buildings, there are thousands of individual standpipe system hose valve outlets throughout each of these buildings.  The specific standpipe system hose valve outlet on the tenth floor, a completely different one on the fiftieth floor, and countless others in between.  Do you have any idea how each of these individual hose valve outlets are going to perform in the “heat of battle”?  Specifically, what will be the outlet pressure and flow (gpm) from any specific hose valve outlet?  Unless you have flow tested a specific hose valve outlet, you simply have no idea what the flow pressure and volume are going to be, usually only discovering the facts of flow and pressure on the night you have a fire in that building.

It would simply be impractical to conduct a thorough analysis of each and every hose valve outlet, within each and every standpipe-equipped building in most cities.  However, the bottom line is this, make no mistake, the volume and pressure may or may not be sufficient enough to combat a serious fire.

Although we cannot conduct a flow test of each individual hose valve outlet, we can utilize several pieces of reliable information to make an educated guess regarding the likely hose valve outlet pressure and volume.  We can begin to understand the low pressure design of standpipe systems by taking a closer look at NFPA #14, which for years has served as a guide for fire protection engineers when designing and installing standpipe systems.  In a nutshell, for NFPA #14 required a flow pressure of 65psi at the topmost (or the most remote standpipe system hose valve outlet) with 500gpm flowing, specifically for buildings built prior to 1993.  There are a whole lot of high-rise and standpipe equipped buildings out there in our fire service world, that were built prior to 1993, with standpipe systems designed around that criteria.  In addition, NFPA #14 requires 100psi at the top most outlet with 500gpm flowing, for buildings built today, and all buildings built post 1993.  One need not be a hydraulics expert to clearly understand that there is a finite amount of pressure, and that limited amount of pressure might not be enough to overcome the friction loss in small and medium diameter hoseline (1 ½ and 1 ¾-inch) and achieve the necessary nozzle pressure in order to ultimately produce a safe and effective fire stream.

In addition, there are numerous other factors that are for the most part out of our control that may also negatively affect standpipe system hose valve outlet pressure.  Not the least of which are standpipe system pressure regulating devices, specifically, standpipe system pressure reducing valves (PRVs), and standpipe system pressure restricting devices (PRDs).  Add to this the long list of potential human error within the design and maintenance of a standpipe system, and you have a serious potential problem, that we are left to discover and deal with in the heat of battle.

Utilizing the analogy of the fire triangle, I instruct firefighters, company officers, and chief officers to make their high-rise / standpipe operational size-up as simple as possible.  I call this the Standpipe Operations Triangle.  At the base of the triangle, serving as the foundation of the triangle is Standpipe System Pressure.  Once again, this should be a huge question mark, of which we simply don’t have the precise and accurate information regarding pressure and volume at a specific hose valve outlet, unless we have previously flow tested, that specific hose valve outlet.

Forming the right hand leg of the triangle is modern Fuel Loads.  The dedicated firefighter, who spends time studying and learning “how to do the job”, is keenly aware of the fact that the fires we fight today are more dangerous and complicated due primarily to modern fuels.  Specifically, the plastics and hydrocarbons that make up much of the modern fire environment create a situation where the BTU production is much greater and there is a much more rapid heat release rate than ever before.

The last component of the Standpipe Operation Triangle is time, or specifically, Reflex Time.  The time needed to get a handline in position and in-service, delivering water, in the form of a safe and effective fire stream, onto a fire on an upper floor of a high-rise building.  How long does that take?  Ask yourself the question, and give an honest answer.  From the time your engine company engineer/driver sets the air brake at the street level, until the attack team is putting water on the fire on the twentieth floor, how long is that?  It could be twenty minutes or longer.

As I said at the beginning, perhaps part of this overall failure can and should be addressed by choosing the proper weapon to utilize when operating off a standpipe system.  We’re talking high volume low-pressure weapon selection.  Ultimately, my final recommendation for you is this; due to all of these low-pressure factors, we must equip ourselves properly, with the appropriate weapon, in order to have the greatest chance for success and safety during high-rise fire attack when utilizing a low-pressure standpipe system.  Our greatest chance for success and safety requires the use of 2 ½-inch attack hoseline.  It’s as simple as that.  Yes, we’ve all heard it before from the naysayers who have convinced themselves and others around them that 2 ½-inch attack hoseline is too hard to move.  They make statements like “this isn’t New York”, or “we don’t have enough manpower to do that”.  Please stay tuned.  In my next several articles, I will give you a proven recipe for success with 2 ½ -inch hose for high-rise / standpipe operations.  And yes, you can do it!  But first you must believe, and then you must train.  Next time I’ll introduce you to the “Denver HosePack”.  Stay low!

 

 

 

 

 

 

 

 


by

Tags: